Table A.10.2.2 Interior Finish Classification Limitations
Occupancy Exits Exit Access Corridors Other Spaces
Assembly >300 occupant load A A or B A or B
I or II I or II NA
Assembly ≤300 occupant load A A or B A, B, or C
I or II I or II NA
Educational — New A A or B A or B; C on low partitions†
I or II I or II NA
Day-Care Centers — New A A A or B
I or II I or II NA
Day-Care Homes — New A or B A or B A, B, or C
I or II   NA
Health Care — New A A A
NA B on lower portion of corridor wall† B in small individual rooms†
I or II I or II NA
Detention and Correctional — New
(sprinklers mandatory)
A or B A or B A,B,or C
I or II I or II NA
One- and Two-Family Dwellings and
Lodging or Rooming Houses
A, B, or C A, B, or C A, B, or C
Hotels and Dormitories — New A A or B A,B,or C
I or II I or II NA
Apartment Buildings — New A A or B A,B,or C
I or II I or II NA
Residential Board and Care —
(See Chapters 32 and 33.)
     
Mercantile — New A or B A or B A or B
I or II   NA
Business and Ambulatory
Health Care — New
A or B A or B A,B,or C
I or II   NA
Industrial A or B A,B,or C A,B,or C
I or II I or II NA
Storage A or B A,B,or C A,B,or C
I or II   NA

NA: Not applicable.

Notes:

TableA.10.2Fire Testing of Interior Finish Materials
Material Test Method Acceptance Criterion Application Requirement Section
Interior wall and ceilingfinish materials,exceptas shown in this table ASTM E 84 or ANSI/UL723 Class A,in accordance with 10.2.3.4 (1) As required by relevantsections 10.2.3
ASTM E 84 or ANSI/UL723 Class B,in accordance with 10.2.3.4 (2) As required by relevantsections 10.2.3
ASTM E 84 or ANSI/UL723 Class C,in accordance with 10.2.3.4 (3) As required by relevantsections 10.2.3
NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.3.2
Materials having thickness < 1/28 in. (0.90 mm) applied directly to the surface of walls or ceilings No testing required     10.2.1.2
Exposed portions of structural members complying with requirements for buildings of Type IV (2HH) construction in accordance with NFPA220 No testing required     10.2.3.1
Cellular or foamed plastics(exposed foamed plasticsand foamed plastics usedin conjunction withtextile or vinyl facing orcover) NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.4.3.1.1(1)
ANSI/UL 1715 Pass Permitted where Class A,B,or C is required byrelevant sections 10.2.4.3.1.1(2)
ANSI/UL 1040 Pass Permitted where Class A,B,or C is required byrelevant sections 10.2.4.3.1.1(3)
FM 4880 Pass Permitted where Class A,B,or C is required byrelevant sections 10.2.4.3.1.1(4)
Suitable large-scale fire test that substantiates combustibility characteristics for use intended under actual fire conditions Pass Permitted where Class A,B,or C is required byrelevant sections 10.2.4.3.1
Textile wall coverings NFPA 286 In accordance with 10.2.3.7.2 Permitted where Class A, B, or C is required by relevant sections 10.2.4.1(6)
NFPA 265, Method B In accordance with 10.2.3.7.1 Permitted on walls and partitions 10.2.4.1(5)
ASTM E 84 or ANSI/UL 723 Class A, in accordance with 10.2.3.4 (1) Permitted on walls, but also requires sprinklers per Section 9.7 10.2.4.1(1)
ASTM E 84 or ANSI/UL723 Class A, in accordance with 10.2.3.4 (1) Permitted on partitions not exceeding three-quarters of the floor-to-ceiling height or not exceeding 8ft (2440 mm) in height, whichever is less 10.2.4.1(2)
ASTM E 84 or ANSI/UL723 Class A, in accordance with 10.2.3.4 (1) Permitted to extend not more than 48 in. (1220 mm) above finished floor on ceiling-height walls and ceiling-height partitions 10.2.4.1(3)
ASTM E 84 or ANSI/UL723 Class A,in accordancewith 10.2.3.4 (1) Previously approved existing installations of textile material having a Class A rating permitted to be continued to be used 10.2.4.1(4)
Expanded vinyl wall coverings NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.4.2(6)
NFPA 265,Method B In accordance with10.2.3.7.1 Permitted on walls andpartitions 10.2.4.2(5)
ASTM E 84 or ANSI/UL723 Class A, in accordance with 10.2.3.4 (1) Permitted on walls,but also requires sprinklers per Section 9.7 10.2.4.2(1)
ASTM E 84 or ANSI/UL723 Class A,in accordancewith 10.2.3.4 (1) Permitted on partitions not exceeding three-quartersof the floor-to-ceiling height or not exceeding 8ft (2440 mm) in height,whichever is less 10.2.4.2(2)
ASTM E 84 or ANSI/UL723 Class A,in accordancewith 10.2.3.4 (1) Permitted to extend not morethan 48 in. (1220 mm)above finished floor onceiling-height walls andceiling-height partitions 10.2.4.2(3)
ASTM E 84 or ANSI/UL723 Class A,B,or C,inaccordance with 10.2.3.4 Existing installations ofmaterials with appropriatewall finish classificationfor occupancy involved,and with classification inaccordance with theprovisions of 10.2.3.4 10.2.4.2(4)
Textile ceiling coverings NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.4.1(6)
ASTM E 84 or ANSI/UL723 Class A,in accordancewith 10.2.3.4 (1) Permitted on walls,but alsorequires sprinklers perSection 9.7 10.2.4.1(1)
ASTM E 84 or ANSI/UL723 Class A,in accordancewith 10.2.3.4 (1) Previously approved existinginstallations of textilematerial having a Class Arating permitted to becontinued to be used 10.2.4.1(4)
Expanded vinyl ceilingcoverings NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.4.2(6)
ASTM E 84 or ANSI/UL723 Class A,in accordancewith 10.2.3.4 (1) Permitted on walls,but alsorequires sprinklers perSection 9.7 10.2.4.2(1)
ASTM E 84 or ANSI/UL723 Class A,B,or C,inaccordance with 10.2.3.4 Existing installations ofmaterials with appropriatewall finish classificationfor occupancy involved,and with classification inaccordance with theprovisions of 10.2.3.4 10.2.4.2(4)
Interior trim,other thanfoamed plastic andother than wall base ASTM E 84 or ANSI/UL723 Class C,in accordancewith 10.2.3.4 Interior wall and ceiling trimand incidental finish,otherthan wall base not inexcess of 10 percent of theaggregate wall and ceilingareas of any room or spacewhere interior wall andceiling finish of Class A orClass B is required 10.2.5.1
NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.3.2
Foamed plastic used asinterior trim ASTM E 84 or ANSI/UL723 Flame spread index ≤75

(1) Minimum density ofinterior trim required tobe 20 lb/ft3(320 kg/m3)

(2) Maximum thickness ofinterior trim required tobe 1/2in. (13 mm),andmaximum width requiredto be 4 in. (100 mm)

(3) Interior trim notpermitted to constitutemore than 10 percent ofthe wall or ceiling areaof a room or space

10.2.4.3.2

 

10.2.4.3.2

 

10.2.4.3.2

NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A,B,or C is required byrelevant sections 10.2.3.2
Fire-retardant coatings NFPA 703 Class A,B,or C,when tested by ASTM E 84 orANSI/UL 723,inaccordance with 10.2.3.4 Required flame spread orsmoke developmentclassification of existingsurfaces of walls,partitions,columns,andceilings permitted to besecured by applyingapproved fire-retardantcoatings to surfaces havinghigher flame spread ratingsthan permitted; suchtreatments required to betested,or listed and labeledfor application to materialto which they are applied 10.2.6.1
Carpet and carpetlikeinterior floor finishes ASTM D 2859 Pass All areas 10.2.7.1
Floor coverings,otherthan carpet,judged torepresent an unusualhazard (excludingtraditional finish floorsand floor coverings,such as wood flooringand resilient floorcoverings) NFPA 253 Critical radiant flux ≥0.1W/cm2 All areas 10.2.7.2
Interior floor finish,otherthan carpet andcarpetlike materials NFPA 253 Class I:Critical radiantflux ≥0.45 W/cm2,inaccordance with 10.2.7.4 As required by relevantsections 10.2.7.3
NFPA 253 Class II:Critical radiantflux ≥0.22 W/cm2,inaccordance with 10.2.7.4 As required by relevantsections 10.2.7.3
Wall base [interior floor trim material used at junction of wall and floor to provide a functional or decorative border, and not exceeding 6 in. (150mm) in height] NFPA 253 Class II:Critical radiantflux ≥0.22 W/cm2,inaccordance with 10.2.7.4 All areas 10.2.5.2
NFPA 253 Class I:Critical radiantflux ≥0.45 W/cm2,inaccordance with 10.2.7.4 If interior floor finish isrequired to meet Class Icritical radiant flux 10.2.5.2
Floor finish of traditionaltype,such as woodflooring and resilientfloor coverings No testing required     10.2.2.2